Thermocouple and resistor for electric station
type flue, duct thermocouple
type flue, duct thermocouple
产品概述

type flue, duct thermocouple is mainly used for power plant or power plant equipment pipe exhaust  smoke  temperature measurement. It uses a thick protective tube and large diameter connection thread to improve the resistance to flue gas scouring and smoke machine vibration capacity, the measurement side use of reduced type to reduce the thermal response time.


type flue, duct thermocouple with separate protective tube structure, elastic compression measurement components, with aluminum waterproof junction box, and other models of the junction box optional.


  It has the following characteristics:


1) All use of armored components, pressure shock, stability, long life;


2) It’s elastic compacting structure between armored component and bottom of protecting tube

shorten the heat response time and enhance its anti-seismic capacity.

 

3) Large cavity junction box and novel wiring devices make wiring more reliable and easy.


4)The main body and protecting tube are detached structure. So that the user can change the temperature  component when it’s working.

 

5. Deep blind hole processed overall protecting tube with uniform thickness in the bottom, without welding stress or intergranular corrosion hidden dangers. It’s pressure and shock proof, reliable and enduring. It can guarantee the safe work of machine set.    

 


技术参数

1) model specifications

Type

output

Graduation

measuring range

Precision Level

Nominal Pressure

MPa

Protective tube material

WRNR-12

Single

K

0~800

Ⅰor  Ⅱ

9.8

06Cr18Ni11Ti

WRNR2-12

Double branch

WRER-12

Single

E

0~700

WRER2-12

Double branch

2) standard size

Type

Graduation

Protective tube specifications

Process connection

length

(Total length×Insertion depth)/mm

Junction box form

Electric Interface

Reduced part size/mm

Exposed pipe/mm

WRNR-12

K

φ28×φ16×46

φ20×250

ZG2”、NPT2”

M60×3

480×230

680×430

880×630

1380×1130

Terminal Box

Single:M20×1.5,Cable diameterφ10,Double branch:M24×1.5,Cable diameterφ16

WRNR2-12

WRER-12

E

WRER2-12

Note:Other specifications can also be provided upon request